Product Finder > Compressor & Assemblies > Compressors > Reciprocating Compressor > Single Stage Compressor

Bitzer semi-hermetic compressor CE8 8GE-60Y-40P 400V

Order Number:
BRC045
Manufacturer Number:
8GE-60Y
Price:

Product Description

A closely stepped range of compressors for modern refrigeration, air conditioning and heat pump systems. With its new BITZER ECOLINE series, BITZER offers high-efficiency universal compressors that satisfy the demands of modern refrigeration systems:

• Extended range of applications

• Energy efficient

• Cost-effective power regulation

• Wear-resistant drive mechanism

• Quiet and low-vibration

• Minimal space requirements

• Robust

BITZER ECOLINE compressors for operation with frequency inverters up to 70 Hz

All BITZER ECOLINE compressors are designed and optimised for 70 Hz operation. Depending on the refrigerant used and the environmental conditions, a compressor with a PW standard motor (400 V, 3-50 Hz) can be used, or a special motor (230V/400V, 3-50 Hz*) may be required and connected in a delta circuit (230 V, 3-50 Hz). The latter is the case for compressors using version 1 and 2 motors where they are to be operated throughout the entire documented area.

Technical Data

Dimension

Length: 485 mm

Width: 886 mm

Height: 539    mm

General Information

CR Levels: 75 / 50%

Number of Cylinders: 8 pcs

Refrigerant: R134a, R1234yf, R404A, R507A

Engine Version: 1

Series: CE8

Compression Type: Hubkolben

Electrical Data

Starting Current (Locked Rotor): 349.0 A

Supply voltage: 400/3/50 V/Ph/Hz

Max. Operating Current: 113.0 A

Max. Power Consumption: 63.0 kW

Weight

352.00 kg

Flow Volume

185,00 m3/h

Pipe Connections

Discharge Line: 42.0 mm (1 5/8 inch)

Suction Line: 76.0 mm (3 1/8 inch)

Volume

Oil Charge: BSE32

• Option: BSE55 with R134a, R1234yftc > 70֯ COil Quantity: 5.0 l

Additional Information

Note 1: Motor for partial winding start-up Part Winding (PW) Y/YY or ?/??4VES-6Y ... 6FE-50Y Winding Pitch 50%/50% - 380-420V PW YY-3Ph-50Hz - 440-480V PW YY-3Ph-60Hz

Note 2: 8GE-50Y ... 8FE-70Y ?/?? Winding pitch 60 %/40 % - 380-420 ??/3/50 - 440-460 ??/3/60For PW start-up, design motor contactors to approx. 60 % of the maximum operating current.

Note 3: Explanation 1. 2KES-05Y - 4BES-9Y - 220-240V ?/3Ph/50Hz - 380-420V Y/3Ph/50Hz4VES-6Y - 8FE701Y - 265-290V ?/3Ph/60Hz - 440-480V Y/3Ph/60Hz

Accessory

Accessory 1: Control valve for power controller

Accessory 2: Crankcase heater Beer level regulator

Accessory 3: Druckmessumformer

Accessory 4: IQ-Modul Pressure transducer

Accessory 5: Motor Protection Pressurised gas temperature sensor

Accessory 6: Oil pressure safety switch Refrigerator oil

Accessory 7: Option: Refrigerator oil BSE55 with R134a, tc > 70֯ C

Get a Quick Quotation

Thank you for your inquiry!
Our regional team member will contact your shortly.
Oops! Something went wrong while submitting the form.