Certified according to the European Pressure Equipment Directive 2014/68/EU
Heat exchanger pipes: made from Cu or Cu-Ni (saltwater resistant version) with newly developed pipe geometry and a "low fouling" profile on the cooling medium side
Diameter: 216 mm
• R134A: 30.6 kg
• R404A: 26.6 kg
• R22: 30.2 kg
• 2 pass: G 2 Inch
• 4 pass: G 11/4 Inch
• 2 pass: G 2 Inch
• 4 pass: G 11/4 Inch
• Outlet: 1.3/4"-12 Inch
• Inlet: 1.3/4"-12 Inch
65.0 kg
• Dte 10K: 104700 watts
• Dte 15K: 157100 watts
• Dte 10K: 87400 watts
• Dte 15K: 131100 watts
• 2 Pass: 0,30 bar
• 4 Pass: 0,58 bar
• 2 pass: 6.48l/s (23.32- m3/hr)
• 4 pass: 3.24- l/s (11.66- m3/hr)
• Outlet Diameter: 28L mm (1 1/8" inches)
• Inlet Diameter: 35L mm (1 3/8" inches)
• Refrigerant side: 27.7 dm
• Cooling medium side: 7.0 dm
Performance data based on:
Refrigerant: R134a, 2 pass cooling, Refrigerant inlet temperature: 90 oC, Cleanliness factor on cooling medium side: 0.00004 m3K/W Standard version, Condensation temperature: 40 oC. Cooling medium inlet temperature: 29 oC, Salt water resistant version, Condensation temperature: 35 oC, Cooling medium inlet temperature: 25 oC, Condenser capacity is heavily influenced by the conditions in which the system is being operated.
Performance data for other refrigerant and cooling media can be found in the BITZER SOFTWARE.
This performance data assumes a maximum flow speed of 2.0 m/s for the salt water resistant versions
Fluid temperature of 20 oC and container filled to 90%
For welding neck flange DIN2633, PN 10/16 or threaded flange DIN2566, PN 10/16
• Accessory 1: Adapter
• Accessory 2: Rail set bottom
• Accessory 3: Rail set top
• Accessory 4: Upper mounting plate