Certified according to the European Pressure Equipment Directive 2014/68/EU
Heat exchanger pipes: made from Cu or Cu-Ni (saltwater resistant version) with newly developed pipe geometry and a "low fouling" profile on the cooling medium side
Diameter: 216 mm
• R 134a: 40.8 kg
• R 404a: 35.6 kg
• R 22: 40.3 kg
• 2 pass: G 2 Inch
• 4 pass: G 1 1/4 Inch
• 2 pass: G 2 Inch
• 4 pass: G 1 1/4 Inch
• Outlet: 1 5/8 inches
• Inlet: 2 1/4"-12 inches
103 kg
• Dte 10K: 174800 watts
• Dte 15K: 262200 watts
• Dte 10K: 138000 watts
• Dte 15K: 206900 watts
• 2 pass: 0.38 bar
• 4 pass: 0.74 bar
• 2 pass: 8.33 l/s (30.00- m3/hr)
• 4 pass: 4.17- l/s (15.00 - m3/hr)
• Outlet Diameter: 35L mm (1 13/8" inches)
• Inlet Diameter: 42 L mm (1 5/8 inches)
• Refrigerant side: 37.0 dm
• Cooling medium side: 11.5 dm
Performance data based on:
Refrigerant: R134a, 2 pass cooling, Refrigerant inlet temperature: 90 oC, Cleanliness factor on cooling medium side: 0.00004 m3K/W Standard version, Condensation temperature: 40 oC, Cooling medium inlet temperature: 29 oC, Salt water resistant version, Condensation temperature: 35 oC, Cooling medium inlet temperature: 25 oC, Condenser capacity is heavily influenced by the conditions in which the system is being operated.
Performance data for other refrigerant and cooling media can be found in the BITZER SOFTWARE.
This performance data assumes a maximum flow speed of 2.0 m/s for the salt water resistant versions
Fluid temperature of 20 oC and container filled to 90%
For welding neck flange DIN2633, PN 10/16 or threaded flange DIN2566, PN 10/16
• Accessory 1: Adapter
• Accessory 2: Rail Set
• Accessory 3: Upper Mounting Plate