Certified according to the European Pressure Equipment Directive 2014/68/EU
Heat exchanger pipes: made from Cu or Cu-Ni (saltwater resistant version) with newly developed pipe geometry and a �low fouling� profile on the cooling medium sideHeat exchanger pipes ...
Diameter: 216 mm
• 2 pass-G 2 Inch
• 4 pass-G 1 1/4 Inch
• 2 pass-G 2 Inch
• 4 pass-G 1 1/4 Inch
• Outlet1.3?4"-12 Inch
• Inlet-2.1/4"-12 Inch
87.0 kg
• Dte 10K-136400 watts
• Dte 15K-204600 watts
• Dte 10K-107500 watts
• Dte 15K-161300 watts
Pressure drop: 2 pass-0,38 bar
Condenser Capcity: 7.3 kW
• 2 pass: 6.48 l/s (23.32 - m3/hr)
• 4 pass: 3.24- l/s (11.66 - m3/hr)
• Outlet Diameter: 35 mm (1 3/8" inch)
• Inlet Diameter: 42 L mm (1 5/8" inches)
• Refrigerant side: 40.0 dm
• Cooling medium side: 9.3 dm
Performance data based on:
Refrigerant: R134a 2 pass cooling, Refrigerant inlet temperature: 90 oC, Cleanliness factor on cooling medium side: 0.00004 m3K/W Standard version, Condensation temperature: 40 oC, Cooling medium inlet temperature: 29 oC, Salt water resistant version Condensation temperature: 35 oC, Cooling medium inlet temperature: 25 oC, Condenser capacity is heavily influenced by the conditions in which the system is being operated.
Performance data for other refrigerant and cooling media can be found in the BITZER SOFTWARE.
This performance data assumes a maximum flow speed of 2.0 m/s for the salt water resistant versions
Fluid temperature of 20 0C and container filled to 90%
For welding neck flange DIN2633, PN 10/16 or threaded flange DIN2566, PN 10/16 AF152
• Accessory 1: Adapter
• Accessory 2: Rail set bottom
• Accessory 3: Rail set top
• Accessory 4: Upper mounting plate